Shanghai Shenghua Cable (Group) Co., Ltd.
|
Gold Index: 9652
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Application
Medium voltage power cable for static application in ground, within and outside facilities, outdoor, in cable canals, in water, in conditions where cables are not exposed to heavier mechanical stress and tensile strain. Due to its very low factor of dielectric loss, which remains constant over its entire operating lifetime, and owing to excellent insulation property of XLPE-material, firmly longitudinally spliced with inner and external screen of semi-conductive material (extruded in one process), the cable has a high operating reliability. Used in transformer stations, switching blocks, in electric power plants and industrial plants. To avoid the effects of external impact, the adhering semi-conductive layer extruded between conductor and insulation, along with concentric copper conductor, secures restriction of electric field and resistance to partial discharges.
Construction
Conductor: | Cu round conductor, multi wire stranded compacted (RM), class 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295 |
Inner screen: | extruded semi-conductive skin on conductor |
Insulation: | XLPE (cross-linked polyethylene, recent mark: PE-X) compound DIX 8 acc. to HRN HD 620 S1 ili 2XI1 acc. to DIN VDE 0207 dio 22 |
External screen: | extruded semi-conductive skin on insulation, longitudinally spliced with insulation (+tape of semi-conductive material) |
Conductor screen: | copper tape wrapped in counter-helix |
Filler: | fillers strip, yarn, or paper |
Wrapping: | non woven wrapping tape or flame retardant or water proof |
Inner covering: | Extruded PVC |
Armour: | Galvanized Steel Wire |
Overall Sheath | polyvinylchloride (PVC) or FR-PVC, PE, LSOH |
Sheath color | Black, red or customized |
Standards
IEC 60502, 60228, 60332, 60331
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Technical data
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -20°C till +90°C | |
fixed | -20°C till +90°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 50265-2-1 |
Certificates
ISO,CE, KEMA ,IEC, RoHS, CCC, P3C and more others at request
Ordering Advice
Rated Voltage
Application Standard:IEC/BS/UL/GB
Number of Cores
Conductor Size $ Construction
Type of Insulation
Armored or unarmored. If armour, the armour type & material
The Requirement of Sheath
Length of Cable & Packing Requirement
Other Requirement
Specifications
Nom. Cross-section of conductor | Strands No./Dia. Of Conductor | Insulation Thickness | Inner Sheath Thickness | Dia. Of Armor Wire | Sheath Thickness | Approx. O.D. | Approx.Weight | Max. D.C Resistance of Conductor (20 ) | Testing Voltage A.C | Current Rating | |
mm2 | pc/mm | mm | mm | mm | mm | (mm) | kg/km | Ω /km | kV/5min | In air (A) | In soil(A) |
3 × 50 | 10/2.52 | 8 | 1.8 | 3.15 | 3.5 | 80.0 | 9376 | 0.387 | 63 | 175 | 180 |
3 × 70 | 14/2.52 | 8 | 1.8 | 3.15 | 3.6 | 84.0 | 10426 | 0.268 | 63 | 220 | 220 |
3 × 95 | 19/2.52 | 8 | 1.8 | 3.15 | 3.7 | 87.0 | 11475 | 0.193 | 63 | 255 | 265 |
3 × 120 | 24/2.52 | 8 | 1.8 | 3.15 | 3.8 | 90.0 | 12598 | 0.153 | 63 | 290 | <