Shanghai Shenghua Cable (Group) Co., Ltd.
|
Gold Index: 9652
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
1KV Aerial Bundled Cables Aluminium Phase Conductor / Street Lighting Conductor Compact Circular
Construction
1. Conductor:
a) Phase - The phase conductor shall be of H68 Condition aluminium conductor and compacted circular stranded.
b) Neutral or messenger - The Neutral or messenger conductor shall be of aluminium alloy conductor and compacted circular stranded c)Street Lighting- The street lighting conductors shall be of H68 condition aluminium conductor and compacted circular stranded..
2. Insulation:
The phase, neutral conductors shall be extruded with polyethylene(PE) as insulation.
0.6/1(1.2)kV AL/XLPE(PE) Insulated
Aerial Bundled Cables with Street Lighting Conductor
3 Phase conductors + 1 Messenger conductor + 1 Street lighting conductor
Description
The aerial Bundled cables designed for overhead distribution lines have an insulated neutral messenger made of AAAC, which the insulated aluminium phase conductor are helically wound over it. Cables are rated at 0.6/1(1.2)kV and conform to IEC60502.
Phase conductor | |||||||||
Nominal cross-sectional area | mm² | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
Number of cores | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
Minimum number of wires | 6 | 6 | 6 | 12 | 15 | 15 | 30 | 30 | |
Nominal insulation thickness | mm | 1.2 | 1.2 | 1.4 | 1.4 | 1.6 | 1.6 | 1.8 | 2.0 |
Diameter of insulated core | mm | 8.5 | 9.5 | 11.2 | 13.0 | 15.1 | 16.6 | 18.4 | 20.6 |
Max. DC resistance at 20 | ohm/km | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | 0.164 |
Current rating at still wind, ambient | A | 84 | 104 | 129 | 167 | 209 | 246 | 283 | 332 |
temperature=30 | |||||||||
Conductor temperature=75 | |||||||||
Messenger conductor | |||||||||
Nominal cross-sectional area | mm² | 25 | 25 | 35 | 50 | 70 | 70 | 95 | 120 |
Minimum number of wires | 6 | 6 | 6 | 6 | 12 | 12 | 15 | 15 | |
Nominal insulation thickness | mm | 1.2 | 1.2 | 1.2 | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 |
Diameter of insulated core | mm | 8.5 | 8.5 | 9.5 | 11.2 | 13.1 | 13.1 | 15.1 | 16.6 |
Max. DC resistance at 20 | ohm/km | 1.312 | 1.312 | 0.943 | 0.693 | 0.469 | 0.469 | 0.349 | 0.273 |
Calculated breaking load | kN | 6.4 | 6.4 | 8.9 | 12.1 | 18.0 | 18.0 | 24.2 | 30.8 |
Street lighting conductor | |||||||||
Nominal cross-sectional area | mm² | 25 | 25 | 35 | 50 | 70 | 70 | 95 | 120 |
Minimum number of wires | 6 | 6 | 6 | 6 | 12 | 12 | 15 | 15 | |
Nominal insulation thickness | mm | 1.2 | 1.2 | 1.2 | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 |
Diameter of insulated core | mm | 8.5 | 8.5 | 9.5 | 11.2 |
Related Search
Single Conductor Cables
Conductor
Aluminium Conductor Wire
Aluminium Alloy Conductor
Copper Conductor
Aluminum Conductor
More>>
Find more related products in following catalogs on Hisupplier.comCompany InfoShanghai Shenghua Cable (Group) Co., Ltd. [China (Mainland)]
Business Type:Manufacturer You May Like:
Printable Page
Bookmark this page
Sitemap XML About HiSupplier Help Center Customer Service Friend Links Site Map Archives Browse by: China Suppliers - Hot Products - Products Directory - Offers Directory - Suppliers Directory - Buyers Directory Language Option: العربية - Nederlands- Français- Deutsch- Italiano- 日本語- 한국의- Português- Pусский- Español Copyright © HiSupplier.com Online Inc. All Rights Reserved.
|