Post Offer Free
Shanghai Shenghua Cable (Group) Co., Ltd.  

Gold Index: 9652

You are here: home  > PE Insulation Five Core Aerial Drop Cable STANDARD NF C 33-209 NFA 2X

PE Insulation Five Core Aerial Drop Cable STANDARD NF C 33-209 NFA 2X 

Place of Origin: Zhejiang, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: ABC-AL/PE-0.6/1KV 5 Cores

PE Insulation Five Core Aerial Drop Cable STANDARD NF C 33-209 NFA 2X
 
 
 
 

PE Insulation Five Core Aerial Drop Cable STANDARD NF C 33-209 NFA 2X

 

 

 

 

Construction

 

  1. Conductor:

 

a)Phase - The phase conductor shall be of H68 Condition aluminium conductor and compacted circular stranded.

 

b)Neutral or messenger - The Neutral or messenger conductor shall be of aluminium alloy conductor and compacted circular stranded c)Street Lighting- The street lighting conductors shall be of H68 condition aluminium conductor and compacted circular stranded..

 

  1. Insulation:

 

The phase, neutral conductors shall be extruded with polyethylene(PE) as insulation.

 

 

 

 

 

Schedule of technical particulars

 

Phase conductor                  
Nominal cross-sectional area mm² 25 35 50 70 95 120 150 185
Number of cores   3 3 3 3 3 3 3 3
Minimum number of wires   6 6 6 12 15 15 30 30
Nominal insulation thickness mm 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0
Diameter of insulated core mm 8.5 9.5 11.2 13.0 15.1 16.6 18.4 20.6
Max. DC resistance at 20 ohm/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164
Current rating at still wind, ambient A 84 104 129 167 209 246 283 332
temperature=30
Conductor temperature=75                  
Messenger conductor                  
Nominal cross-sectional area mm² 25 25 35 50 70 70 95 120
Minimum number of wires   6 6 6 6 12 12 15 15
Nominal insulation thickness mm 1.2 1.2 1.2 1.4 1.4 1.4 1.6 1.6
Diameter of insulated core mm 8.5 8.5 9.5 11.2 13.1 13.1 15.1 16.6
Max. DC resistance at 20 ohm/km 1.312 1.312 0.943 0.693 0.469 0.469 0.349 0.273
Calculated breaking load kN 6.4 6.4 8.9 12.1 18.0 18.0 24.2 30.8
Street lighting conductor                  
Nominal cross-sectional area mm² 25 25 35 50 70 70 95 120
Minimum number of wires   6 6 6 6 12 12 15 15
Nominal insulation thickness mm 1.2 1.2 1.2 1.4 1.4 1.4 1.6 1.6
Diameter of insulated core mm 8.5 8.5 9.5 11.2 13.1 13.1 15.1 16.6
Max. DC resistance at 20 ohm/km 1.312 1.312 0.943 0.693 0.469 0.469 0.349 0.273
bigPhoto
 Mr. Ms. Mayling Zhao

Tel: 86-21-68172999
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Shanghai Shenghua Cable (Group) Co., Ltd. [China (Mainland)]


Business Type:Manufacturer
City: Shanghai
Province/State: Shanghai
Country/Region: China (Mainland)

You May Like:

Product (197)